548J
PACKAGED HEAT PUMP
3 TO 8.5 NOMINAL TONS
Product Data
C08515
(Optional hail guard shown.)
This product has been designed and manufactured to
meet Energy Star® criteria for energy efficiency.
However, proper refrigerant charge and proper air flow
are critical to achieve rated capacity and efficiency.
Installation of this product should follow all
manufacturer’s refrigerant charging and air flow
instructions. Failure to confirm proper charge and
air f low may reduce energy efficiency and shorten
equipment life.
the environmentally sound refrigerant
Page view 0
1 2 3 4 5 6 ... 75 76

Summary of Contents

Page 1 - Product Data

548JPACKAGED HEAT PUMP3 TO 8.5 NOMINAL TONSProduct DataC08515(Optional hail guard shown.)This product has been designed and manufactured tomeet Energy

Page 2 - TABLE OF CONTENTS

10Table 5 – PHYSICAL DATA (COOLING) 3 -- 6 TONS548J*04 548J*05 548J*06 548J*07Refrigeration System#Circuits/#Comp./Type 1/1/Scroll 1/1/Scroll 1/1/Scro

Page 3 - FEATURES AND BENEFITS

11Table 6 – PHYSICAL DATA (COOLING) 7.5 -- 8.5 TONS548J*08 548J*09Refrigeration System#Circuits/#Comp./Type 2/2/Scroll 2/2/ScrollPuronr refrig. (R---

Page 4 - MODEL NUMBER NOMENCLATURE

12Table 7 – ELECTRIC HEAT -- ELECTRICAL DATA 3 TONSUNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERPART NUMBERCRHEATERXXXXXXNOMPWR(kW)APPPWR(kW)SIN

Page 5

13Table 7 -- (cont.) ELECTRIC HEAT -- ELECTRICAL DATA 4 TONSUNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERPART NUMBERCRHEATERXXXXXXNOMPWR(kW)APPP

Page 6

14Table 7 -- (cont.) ELECTRIC HEAT -- ELECTRICAL DATA 5 TONSUNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERPART NUMBERCRHEATERXXXXXXNOMPWR(kW)APPP

Page 7 - Thru--the--Base Connections

15Table 7 -- (cont.) ELECTRIC HEAT -- ELECTRICAL DATA 6 TONSUNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERPART NUMBERCRHEATERXXXXXXNOMPWR(kW)APPP

Page 8

16Table 7 -- (cont.) ELECTRIC HEAT -- ELECTRICAL DATA 7.5 TONSUNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERPART NUMBERCRHEATERXXXXXXNOMPWR(kW)AP

Page 9

17Table 7 -- (cont.) ELECTRIC HEAT -- ELECTRICAL DATA 8.5 TONSUNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATERPART NUMBERCRHEATERXXXXXXNOMPWR(kW)AP

Page 10

18WEIGHTS & DIMENSIONSC09018Fig. 1 -- Dimensions 548J 04 --07548J

Page 11

19WEIGHTS & DIMENSIONS (cont.)C09019Fig. 2 -- Dimensions 548J 04 --07CBADC08337Fig. 3 -- Service ClearanceLOC DIMENSION CONDITIONA48” (1219 mm) Un

Page 12

2TABLE OF CONTENTSPAGEFEATURES AND BENEFITS 3...MODEL NUMBER NOMENCLATURE 4...FACTORY OPTIONS & ACCESSORIES 5...

Page 13

20WEIGHTS & DIMENSIONS (cont.)548J*04-07AROOFCURBACCESSORYCRRFCURB001A01CRRFCURB002A011’ - 2”[356]2’ - 0”[610]UNIT SIZEC08560Fig. 4 -- Curb Dimens

Page 14

21WEIGHTS & DIMENSIONS (cont.)Horizontal Connections / EconomizerVertical Connections / EconomizerC08679Fig. 5 -- Dimensions 548J 08 --09548J

Page 15

22WEIGHTS & DIMENSIONS (cont.)C08680Fig. 6 -- Dimensions 548J 08 --09CBADC08337Fig. 7 -- Service ClearanceLOC DIMENSION CONDITIONA48” (1219 mm) Un

Page 16

23WEIGHTS & DIMENSIONS (cont.)548J08, 09548J08, 09UNIT SIZEROOFCURBACCESSORYCRRFCURB003A01CRRFCURB004A011’ - 2”[356]2’ - 0”[610]C08561Fig. 8 -- Cu

Page 17

24APPLICATION DATAMin operating ambient temp (cooling):In mechanical cooling mode, your Bryant rooftop cansafely operate down to an outdoor a mbient t

Page 18 - WEIGHTS & DIMENSIONS

25SELECTION PROCEDURE (WITH 548J*07 EXAMPLE)(Selection software by Bryant saves time by performing many of the steps below.)I. Determine cooling and h

Page 19 - Fig. 3 -- Service Clearance

26Table 8 – COOLING CAPACITIES 1--STAGE COOLING 3 TONS548J*04AMBIENT TEMPERATURE85 95 105 115EA (dB) EA (dB) EA (dB) EA (dB)75 80 85 75 80 85 75 80 85

Page 20

27Table 9 – COOLING CAPACITIES 1--STAGE COOLING 4 TONS548J*05AMBIENT TEMPERATURE85 95 105 115EA (dB) EA (dB) EA (dB) EA (dB)75 80 85 75 80 85 75 80 85

Page 21

28Table 10 – COOLING CAPACITIES 1--STAGE COOLING 5 TONS548J*06AMBIENT TEMPERATURE85 95 105 115EA (dB) EA (dB) EA (dB) EA (dB)75 80 85 75 80 85 75 80 8

Page 22 - Fig. 7 -- Service Clearance

29Table 11 – COOLING CAPACITIES 1--STAGE COOLING 6 TONS548J*07AMBIENT TEMPERATURE85 95 105 115EA (dB) EA (dB) EA (dB) EA (dB)75 80 85 75 80 85 75 80 8

Page 23

3FEATURES AND BENEFITSS Up to 28% lighter than similar industry units. Lighter rooftops make easier replacement jobs.S 3 --8.5 ton units fit on existi

Page 24 - APPLICATION DATA

30Table 12 – COOLING CAPACITIES 2--STAGE COOLING 7.5 TONS548J*08AMBIENT TEMPERATURE85 95 105 115EA (dB) EA (dB) EA (dB) EA (dB)75 80 85 75 80 85 75 80

Page 25

31Table 13 – COOLING CAPACITIES 2--STAGE COOLING 8.5 TONS548J*09AMBIENT TEMPERATURE85 95 105 115EA (dB) EA (dB) EA (dB) EA (dB)75 80 85 75 80 85 75 80

Page 26

32Table 14 – HEATING CAPACITIES 3 TONS548J*04RETURNAIR(°Fdb)CFM(STANDARD AIR)TEMPERATURE AIR ENTERING OUTDOOR COIL (°F db at 70% rh)--- 1 0 0 10 17 30

Page 27

33Table 16 – HEATING CAPACITY 5 TONS548J*06RETURNAIR(°FDB)CFM(STANDARD AIR)TEMPERATURE AIR ENTERING OUTDOOR COIL (°F DB AT 70% RH)--- 1 0 0 10 17 30 4

Page 28

34Table 18 – HEATING CAPACITY 7.5 TONS548J*08RETURNAIR(°Fdb)CFM(STANDARD AIR)TEMPERATURE AIR ENTERING OUTDOOR COIL (°F db at 70% rh)--- 1 0 0 10 17 30

Page 29

35Table 20 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories)Economizer3 --- 6 T O N SCFM (in. wg) 600 800 1000 1250 1500 1750 2000 2250 25

Page 30

36FAN PERFORMANCETable 21 – 548J*04 ELECTRIC DRIVE, X13 MOTOR,3 TON HORIZONTAL SUPPLYSPEED(TORQUE)TAPCFM ESP BHP1900 0.70 0.31975 0.60 0.301050 0.50 0

Page 31

37FAN PERFORMANCE (cont.)Table 23 – 548J*05 ELECTRIC DRIVE, X13 MOTOR,4 TON HORIZONTAL SUPPLYSPEED(TORQUE)TAPCFM ESP BHP11200 0.75 0.481300 0.63 0.461

Page 32

38FAN PERFORMANCE (cont.)Table 25 – 548J*06 ELECTRIC DRIVE, X13 MOTOR,5 TON HORIZONTAL SUPPLYSPEED(TORQUE)TAPCFM ESP BHP11500 1.19 0.741625 1.01 0.731

Page 33

39FAN PERFORMANCE (cont.)Table 27 – 548J*04 3 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP

Page 34

4MODEL NUMBER NOMENCLATURE1234567891011121314151617185 4 8 J P 0 6 A 0 0 0 A 0 B 0 A A --____________ ______ ________ ______Unit Type Design Revision5

Page 35 - Electric Heaters

40FAN PERFORMANCE (cont.)Table 29 – 548J*05 4 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP

Page 36 - FAN PERFORMANCE

41FAN PERFORMANCE (cont.)Table 31 – 548J*06 5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP

Page 37 - FAN PERFORMANCE (cont.)

42FAN PERFORMANCE (cont.)Table 33 – 548J*07 6 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM BHP

Page 38

43FAN PERFORMANCE (cont.)Table 35 – 548J*08 7.5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM B

Page 39

44FAN PERFORMANCE (cont.)Table 37 – 548J*09 8.5 TON HORIZONTAL SUPPLYCFMAVAILABLEEXTERNALSTATICPRESSURE(IN.WG)0.2 0.4 0.6 0.8 1.0RPM BHP RPM BHP RPM B

Page 40

45FAN PERFORMANCE (cont.)Table 39 – PULLEY ADJUSTMENTUNIT MOTOR/DRIVE COMBOMOTOR PULLEY TURN S OPEN0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5043phaseMedium Stati

Page 41

46ECONOMIZER, BAROMETRI C RELI EF AND PE PERFORMANCE050010001500200025000 0.05 0.1 0.15 0.2 0.25 0.3RETURN DUCT STATIC PRESS URE (in. wg)RELIEF FLOW (

Page 42

47ELECTRICAL INFORMATIONTable 40 – 548J*04 1--Stage Cooling 3 TONSV--Ph--HzVOLTAGERANGECOMP (ea) OFM (ea) IFMMIN MAX RLA LRA WATTS FLA TYPEMaxWATTSMax

Page 43

48ELECTRICAL INFORMATION (cont.)Table 43 – 548J*07 1--Stage Cooling 6 TONSV --- P h --- H zVOLTAGERANGECOMP (ea) OFM (ea) IFMRLA LRA WATTS FLA TYPEMax

Page 44

49Table 46 – MCA/MOCP DETERMINATION WITHOUT C.O. OR UNPWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITH OUT C.O. or U NPWR C.O.Nom(kW)FLAWIT

Page 45

5FACTORY OPTIONS AND/OR ACCESSORIESTable 1 – FACTORY--INSTALLED OPTIONS AND FIELD--INSTALLED ACCESSORIESCATEGORY ITEMFACTORYINSTALLEDOPTIONFIELDINSTAL

Page 46 - AIRFLOW (cfm)

50Table 46 – (cont.) M CA/MOCP DETERMINATION WITHOUT C.O. OR UNPWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITHOUT C.O. or UNPWR C.O.Nom(kW

Page 47 - ELECTRICAL INFORMATION

51Table 46 – (cont.) M CA/MOCP DETERMINATION WITHOUT C.O. OR UNPWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITHOUT C.O. or UNPWR C.O.Nom(kW

Page 48

52Table 46 – (cont.) M CA/MOCP DETERMINATION WITHOUT C.O. OR UNPWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITHOUT C.O. or UNPWR C.O.Nom(kW

Page 49

53Table 46 – (cont.) M CA/MOCP DETERMINATION WITHOUT C.O. OR UNPWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITHOUT C.O. or UNPWR C.O.Nom(kW

Page 50

54Table 46 – (cont.) M CA/MOCP DETERMINATION WITHOUT C.O. OR UNPWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITHOUT C.O. or UNPWR C.O.Nom(kW

Page 51

55Table 47 – MCA/MOCP DETERMINATION WITH PWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITH PWRD C.O.Nom(kW)FLAWITHOUT P.E. WITH P.E.MCA MOCP

Page 52

56Table 47– (cont.) MCA/M OCP DETERMINATION WITH PWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITH PWRD C.O.Nom(kW)FLAWITHOUT P.E. WITH P.E.

Page 53

57Table 47 – (cont.) M CA/MOCP DETERMINATION WITH PWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELEC. HTR WITH PWRD C.O.Nom(kW)FLAWITHOUT P.E. WITH P.E

Page 54

58Table 47 – (cont.) M CA/MOCP DETERMINATION WITH PWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER WITH PWRD C.O.Nom(kW)FLAWITHOUT P.E. WI

Page 55

59Table 47 – (cont.) M CA/MOCP DETERMINATION WITH PWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER WITH PWRD C.O.Nom(kW)FLAWITHOUT P.E. WI

Page 56

6FACTORY OPTIONS AND/OR ACCESSORIES (cont.)Economizer (dry--bulb or enthalpy)Economizers save money. They bring in fresh, outside airfor ventilation;

Page 57

60Table 47 – (cont.) M CA/MOCP DETERMINATION WITH PWRD C.O.UNITN O M . V --- P H --- H ZIFMTYPEELECTRIC HEATER WITH PWRD C.O.Nom(kW)FLAWITHOUT P.E. WI

Page 58

61TYPICAL WIRING DIAGRAMSC09063Fig. 17 -- 1--Stage Cooling Typical Power Diagram548J

Page 59

62C09065Fig. 18 -- 2--Stage Cooling Typical Power Diagram548J

Page 60

63C09067Fig. 19 -- Multi--Protocol Option Diagram548J

Page 61 - TYPICAL WIRING DIAGRAMS

64C09062Fig. 20 -- 1--Stage Typical Wiring Diagram548J

Page 62

65C09064Fig. 21 -- 2--Stage Typical Wiring Diagram548J

Page 63

66SEQUENCE OF OPERATIONCooling, unit without economizerWhen thermostat calls for cooling, terminals G and Y1 areenergized. The indoor-fan contactor (I

Page 64

67At the end of the defrost cycle, the electric heaters (ifinstalled) wil l be deenergize d; the reversing valves switchand the outdoor-fan motor will

Page 65

68GUIDE SPECIFICATIONS -- 548J*04--09Note about this specification:Bryant created this specification in “Masterformat” as published by the Constructio

Page 66 - SEQUENCE OF OPERATION

697. Shall have an LED display independently showing the status of serial comm unication, running, errors, power, alldigital outputs, and al l analog

Page 67 - Emergency heat

7FACTORY OPTIONS AND/OR ACCESSORIES (cont.)Motormaster Head Pressure ControllerThe Motormaster motor controller is a low ambient, headpressure control

Page 68 - Rooftop Packaged Heat Pump

7023 40 13 Panel Air Filters23 40 13.13 Decentralized, Rooftop Units:23 40 13.13.A. Standard filter section1. Shall consist of factory--installed, low

Page 69

715. Unit shall be fa ctory configured for vertical supply & return configurations.6. Unit shall be fi eld convertible from vertical to horizontal

Page 70

722. Optional Pre--coated aluminum--fin condenser coils: on all models.a. Shall have a durable epoxy--phenolic coating to provide protection in mildly

Page 71

733. Shall consist of factory--installed, low velocity, throw-- away 2 --in. thick fiberglass filters.4. Filters shall be standard, commercially avail

Page 72

74n. Economizer controller shall accept a 2--10Vdc CO2sensor input for IAQ/DCV control. In this mode, dampersshall modulate the outdoor--air damper to

Page 73

759. Fan/Filter Status Switch:a. Switch shall provide status of indoor evaporator fan (ON/OFF) or filter (CLEAN/DIRTY).b. Status shall be displayed ei

Page 74

76(2.) Heater assemblies are provided with integral fusing for protection of internal heater circuits not exceeding48 amps each. Auto reset thermo lim

Page 75

8Table 2 – ARI COOLING RATING TABLESCOOLING MODE548J*NOMINALCAPACITY(TONS)NET COOLINGCAPACITY(BTUH)TOTALPOWER(kW)SEER EER IPLV04A 3 37,000 3.3 13.40**

Page 76 - Catalog No. PDS548J---01

9Table 3 – MINIMUM -- MAXIMUM AIRFLOWS ELECTRIC HEATUNITCOOLING ELECTRIC HEATERSMINIMUM MAXIMUM MINIMUM MAXIMUM548J*04 900 1500 900 1500548J*05 1200 2