Submit ta l Data
538MAC009 WITH 619MAC009
LEGACY LINEt HIGH--WALL DUCT--FREE SPLIT SYSTEM
COOLING ONLY WITH PURONr REFRIGERANT
Job Data:_________________________________________________ Location:________________________________________
Buyer:________________________________________ Buyer P.O.#_______________________ Carrier # _________________
Unit Number:__________________________________ Model Number: _____________________________________________
Performance Data Certified By: _________________________________________ Date: _______________________________
the environmentally sound refrigerant
FEATURES
S
13 SEER
S Wireless remote standard
S Low voltage controls
S 35 VDC indoor fan motor
S User selectable fan speeds (auto, low med., high)
S Indoor unit is powered from the outdoor unit
S Auto restart
S Diagnostics
S Dehumidification mode
S Turbo Mode
S Sleep mode
S Auto swing
S Timer
S Cleanable filters
S Low ambient operation to -- 20_F (-- 28.9_C) with
accessories
Indoor Unit -- 619MAC / Outdoor Unit -- 538MAC
(Unless otherwise indicated, data applies to both indoor and outdoor models)
SYSTEM SIZE 009...........................................
REFRIGERANT R--410A......................................
PERFORMANCE
Nominal Capacity 9,000.....................................
SEER 13..................................................
Airflow (Low/Med/High) 192 / 260 / 325.........................
Performance at actual conditions: Attached j Not Attached j
SOUND PRESSURE dBA
Indoor (Low/Med/High) 28 / 36 / 42............................
Outdoor 54................................................
SOUND POWER dBA
Indoor (Low/Med/High) 39 / 47 / 53............................
Outdoor 65................................................
ELECTRICAL
System Voltage 115V........................................
MCA (outdoor) 12..........................................
MOCP (outdoor) 20.........................................
Fan Motor (Indoor) (FLA) .1.1.................................
Motor Watts 20.............................................
CONTROLS
Control Remote Wireless.....................................
Control Voltage Low Voltage.................................
Interconnecting (indoor to outdoor) Wiring (0-- 50 ft.) 18 AWG........
Interconnecting (indoor to outdoor) Wiring (50--65 ft.) 16 AWG.......
REFRIGERANT LINES (Insulate both lines)
Mixed Phase Line (in.) OD 1/4................................
Vapor Line (in.) OD 3/8.....................................
Metering/Control Device Capillary tube in outdoor unit.............
Condensate Pump: Required j Not Required j
Low Ambient Controls: Required j Not Required j
Crankcase Heater: Required j Not Required j
Wind Baffle: Required j Not Required j
Optional:
Compressor extended warranty 6--10 years: Required j Not Required j
All parts & labor 2 --5 years: Required j Not Required j
All parts & labor 2 --5 years + Compressor 6 --10 years: Required j Not Required j