  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
Is circuit breaker closed?
Close door switch and go to start.Is red LED status light on? Is door switch closed?
Is red LED status light blinking
rapidly without a pause?
Is there 115v going to switch?
Replace door switch.Replace control center.
Replace transformer.
Is red LED status light blinking
ON/OFF slowly with a
combination of short and long
flashes?
Check for correct line voltage
polarity. If units are twinned,
check for proper low-voltage 
(24v) transformer phasing.
Check for previous fault by 
momentarily shorting the TEST
terminal and the C terminal until
the LED goes out. LED will flash
the status code of any previous
fault or the code No. 11 (1 short
and 1 long flash) if no previous
fault. After the control repeats the
code 3 times, the control will go
through a brief component test
sequence. The inducer will start
and run for the entire component
test. The HSI, blower motor heat
speed, and blower motor cool 
speed will run for 10-15 sec each.
Determine status code. The
status code is a 2 digit number
with the first digit determined by
the number of short flashes and
the second digit by the number of
long flashes.
Once status code is determined,
the control will go through a brief
component test sequence. The
inducer will start and run for the
entire component test. The HSI,
blower motor heat speed, and 
blower motor cool speed will run
for 10-15 sec each.
Was there a previous fault code
other than No. 11?
Does control respond to W, Y,
or G 24-vac thermostat signals?
Run system through a heating or
cooling cycle to check operation.
Status codes are erased after 48
hrs or whenever power (115v
or 24v) is interrupted.
Go to section with status code
determined.
Is there 115v at L1 and L2?
Close circuit breaker and
go back to start.
Check for continuity in wire from circuit
breaker to furnace.
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
NO
YES
YES
YES
START
Is there 24v at SEC-1 and SEC-2?
NO
Is 24 vac present at W, Y, or G
terminals on the control?
Replace control if it does not
respond to 24-vac signal at W, Y,
or G screw terminals.
Check room thermostat or
interconnecting cable.
YES
NO
NO
TROUBLESHOOTING GUIDE
—10—