34
Table 27 Fan Performance, 548F060 High-Static Motor Horizontal Discharge Units
LEGEND
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
4. Maximum continuous bhp is 2.9 and the maximum continuous watts
are 2562. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. See Indoor-Fan Motor Performance,
Table 6 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
6. Interpolation is permissible. Do not extrapolate.
548F060 (5 TONS) HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1500 789 0.40 420 896 0.53 557 990 0.67 704 1072 0.83 872 1153 1.00 1051
1600 826 0.46 483 931 0.61 641 1020 0.75 788 1101 0.91 956 1178 1.09 1145
1700 865 0.54 567 966 0.69 725 1051 0.84 883 1133 1.01 1061 1205 1.18 1240
1800 905 0.62 661 1002 0.78 820 1084 0.93 977 1163 1.10 1156 1235 1.29 1355
1900 945 0.72 757 1037 0.88 925 1119 1.04 1093 1194 1.21 1271 1266 1.40 1471
2000 984 0.82 862 1072 0.98 1030 1154 1.16 1219 1226 1.33 1397 1297 1.53 1608
2100 1024 0.93 977 1108 1.10 1156 1192 1.29 1355 1259 1.47 1545
1327 1.66 1744
2200 1064 1.05 1103 1145 1.22 1282 1225 1.43 1503 1294 1.62 1702
1359 1.80 1902
2300 1104 1.18 1240 1183 1.36 1429 1260 1.57 1650
1330 1.78 1870 1392 1.97 2070
2400 1145 1.32 1387 1222 1.45 1524 1296 1.73 1818
1365 1.94 2038 1426 2.15 2259
2500 1186 1.48 1555 1262 1.68 1765
1331 1.89 1986 1400 2.12 2227 1461 2.34 2459
548F060 (5 TONS) HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1500 1221 1.17 1229 1256 1.30 1366 1283 1.32 1387
1303 1.22 1282 1345 1.34 1390
1600 1252 1.27 1334
1311 1.45 1524 1340 1.58 1660 1330 1.61 1692 1373 1.77 1834
1700 1278 1.37 1439
1345 1.57 1650 1397 1.76 1849 1424 1.89 1986 1470 2.08 2153
1800
1303 1.48 1555 1371 1.69 1776 1433 1.90 1996 1480 2.09 2196 1528 2.30 2381
1900
1330 1.59 1671 1396 1.80 1902 1460 2.03 2133 1517 2.25 2364 1566 2.47 2563
2000
1362 1.73 1818 1422 1.94 2038 1485 2.16 2270 1544 2.40 2522 1594 2.64 2734
2100
1393 1.87 1965 1452 2.08 2185 1510 2.31 2427 1570 2.55 2674 1620 2.80 2905
2200
1423 2.02 2122 1483 2.24 2354 1538 2.46 2585 1594 2.71 2821
1645 2.98 3087
2300
1454 2.18 2291 1515 2.41 2532 1571 2.64 2758 1623 2.88 2976
1675 3.17 3280
2400
1485 2.36 2480 1544 2.59 2721 1604 2.84 2947
1657 3.07 3152 1710 3.38 3497
2500
1518 2.55 2679 1574 2.78 2905
1633 3.03 3134 1692 3.28 3345 1746 3.61 3736
Bhp
Brake Horsepower Input to Fan
FIOP
Factory-Installed Option
Watts
Input Watts to Motor
Page view 33