Bryant Outdoor Heating Unit 379A User Manual Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 8
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
local code governing such wiring. Field low voltage
connections are to be made in accordance with the
wiring diagram shown in Figure 8.
A separate electrical line should be run for this in
stallation and should contain a fused switch in a con
venient location. Refer to Electrical Connections
(Table III) on page 2 for maximum fuse size and
minimum wire size. Field wiring connections are
made in the control box located in the blower com
partment. See Figure 5.
NOTE: If aluminum conductors are used, the con
nections must be made in accordance with the
National Electric Code. Aluminum wire connections
must be made with special connectors. In preparing
the wire just before installing the connector, all
aluminum wire must be “brush-scratched” and the
wire coated with a corrosion inhibitor, such as “Pen-
trox A.” When it is suspected that the connection will
be exposed to moisture, it is very important to cover
the entire connection completely to prevent an electro
chemical action that will cause the connection to fail
very quickly. Reducing the effective size of the wire,
such as cutting off strands so that the wire will fit a
connector, is very poor practice. Proper size con
nectors should be used.
Wiring entrances are provided in the left side of the
unit. Wiring entrances to the unit are shown in the
dimensional drawing on page 2.
NOTE: The wiring entrances to the unit must be
weathertight.
Use thermostat and subbase assembly P/N
34427D031. Set thermostat heat anticipator at 0.8
amps.
VII. STARTUP AND ADJUSTMENTS
Before starting the unit, make sure the gas pipe is
purged and free from air. Do not purge into the com
bustion chamber. All gas piping should be leak tested.
CAUTION: Remove shipping bolt from blower as
described on label attached to blower access panel.
WARNING: Never use a match or other open flame
to check for gas leakage.
Refer to chiller installation instructions for a circuit
description of the cooling section.
The sequence of control operation for the furnace is as
follows:
1. Turn on electrical power and gas supply to unit.
2. Refer to Figure 7. Note that the 24V control circuit
voltage is applied across unit terminals 4 and X when
power is turned on to the furnace.
When the pilot gas cock is opened, the pilot pressure
switch closes and completes the circuit to the glow coil
of pilot assembly (6B) which ignites the pilot Ap
proximately one minute after the pilot is ignited, heat
from the pilot causes the pilot assembly’s normally
closed contacts to open and the normally open con
tacts to close. This action breaks the ignition circuit
and makes the control circuit to the gas valve.
When the thermostat calls for heating, terminal 4 is
connected to terminal W through the thermostat. This
completes the circuit to the gas valve (5B) and to the
heating blower relay (2G). The energized gas valve
opens and supplies gas to the burners. The contacts of
the energized heating blower relay close and make the
line voltage circuit to the blower motor (3A) and,
starts the blower fan.
Pilot Safety Test
If the pilot should go “out”, the pilot assembly’s nor
mally open contacts (which were closed by pilot
ignition) will reopen and break the circuit to the gas
valve. The de-energized gas valve will close and
shutoff the gas supply to the burners.
This safety feature can be checked by closing the pilot
gas cock. The -burners should shutoff within 90
seconds.
NOTE: The pilot will reignite automatically by
means of glow coil ignition when the pilot gas cock is
opened again. There will be a short time delay before
pilot reignition occurs.
Limit Control
The function of the hi-temp limit control (7K) is to
shutoff the gas supply to the burners and maintain an
electrical circuit to the blower motor if the furnace
becomes overheated. The limit control can be checked
by gradually blocking off the return air after the fur
nace has been operating for at least five minutes. As
soon as the limit has functioned to shutoff the gas
valve, unblock the return air opening to permit nor
mal air circulation.
Blower Fan Relay (Heating)
The heating blower fan relay (2G) is located in the
control box and is adjustable to permit lengthening or
shorting the “OFF” cycle. The “ON” cycle is
automatically adjusted as the “OFF” cycle is changed.
The fan control adjusting lever is factory-set at the
center position and should give optimum performance
in most installations. However, on unusual in
stallations or where the line voltage is considerably
above or below the rated output, it may be necessary
to increase or decrease the length of time the blower
remains on. For longer blower operation, move the
adjusting lever toward the “MAX OFF” position. In
this position the control line switch makes contact
sooner and takes the maximum time to break contact.
For shorter blower operation, move the lever in the
opposite direction.
Blower Fan Relay (Codling)
The unit is also equipped with a cooling blower fan
relay (2A). When a chiller is used in conjunction with
the furnace to form a combination heating and
cooling system, this relay is energized by the chiller
transformer when there is a demand for cooling.
— 5 39379D36
Page view 4
1 2 3 4 5 6 7 8

Comments to this Manuals

No comments