Bryant HRVBBLHU User Manual

Browse online or download User Manual for Household fans Bryant HRVBBLHU. HRVBBLHU HRVBBSVC HRVBBLVU

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
SINGLE-PACKAGE
ELECTRIC HEATING
COOLING UNITS
HRVBBLHU
HRVBBSVC
HRVBBLVU
Heat Recovery Ventilators
Form No. PDS HRV.71.2
The Heat Recovery Ventilation (HRV) system offered by Bryant
is the finest unit on the market today.
The HRVB provides efficient and cost-effective heat recovery
during the heating season when needed most.
As temperatures drop below 23°F (–5°C), indoor air is
recirculated periodically through the heat exchanger core to
prevent frost from forming. Competitors’ methods of
supplementary electric defrost waste energy. Unlike rotary
wheel heat exchangers which mix air streams, these cross flow
or counterflow heat exchangers ensure that there is no mixing
of the stale air stream with the fresh outdoor air stream.
A filter installed on the incoming outdoor air stream removes
large airborne particles from the intake air stream before they
enter the heat exchanger and reduces the maintenance
required.
The units’ acoustically engineered design makes them the
quietest on the market and ensures that comfort is felt, not
heard.
Unlatching 2 suitcase style latches allows easy removal of the
filters and core for cleaning.
Note: The HRV should not be installed in an attic or
unconditioned space unless provisions are made for drainline
freezing and unit condensation.
FEATURES
Energy saving defrost cycle
Cross flow, counterflow heat exchangers
Two filters on incoming outdoor air stream to protect the
HRV core
Acoustical design
No-tools maintenance
Polypropylene heat exchanger core
HRVBBSVC
HRVBBLHU
HRVBBLVU
Page view 0
1 2 3 4 5 6 ... 11 12

Summary of Contents

Page 1 - HRVBBLVU

SINGLE-PACKAGEELECTRIC HEATINGCOOLING UNITS HRVBBLHUHRVBBSVCHRVBBLVU Heat Recovery VentilatorsForm No. PDS HRV.71.2 The Heat Recovery Ventilation (HR

Page 2 - Model number nomenclature

—10— COOLING LOAD BTU The cooling load chart shows loads in Btuh. To use the cooling load chart, first find the design enthalpy from a psychrometric ch

Page 3 - ACCESSORIES

—11—.025.024.023.022.021.020.019.018.017.016.015.014.013.012.95.90.85.80.75.70.65.60.55.50.45.40.35.011.010.009.008.007.006.005.004.003.002.0010Sensib

Page 4

—12—SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICEUNIT MUST BE INSTALLED IN ACCORDANCEWITH INSTALLATION INSTRUCTIONSCancels: PDS HRV.71.1Form/Catalog

Page 5 - DIMENSIONS

—2— Model number nomenclature HRV BB LHU 1 150 Maximum Capacity (CFM)150 CFM200 CFM250 CFM330 CFMElectrical Supply:1 — 115 voltsDescriptor:LHU — Larg

Page 6 - DIMENSIONS (continued)

—3— Controls and accessories part no. nomenclature ACCESSORIES K V B CN 01 01 BAUCONTROL DESCRIPTION BAU — Bryant Automatic ControlBBS — Bryant Basic

Page 7 - HRVBBLVU1200 or HRVBBLVU1330

—4— CONTROL FEATURES Basic Control: Allows the user to manually set fan speed to low or high as required to maximize comfort. Standard Control: Off

Page 8 - ELECTRICAL DATA

—5— 20"(508.0)15"(381.0)4 3/4"(120.6)30 1/4"(768.3)2 5/16"(58.7)18 1/8"(460.4)16 7/8"(428.6)1. FRESH AIR FROM OUTS

Page 9 - HEATING LOAD BTU

—6— 5 3⁄4″[146.0]D227″[685.8]22 1/16″[560.4] 1″[25.4]2 PLCS15 11⁄16″[398.5] E3141 15⁄16″[23.8]3 3⁄16″[81.0]4 9⁄16″[115.9)]F DIA2 PLCS19 3

Page 10 - COOLING LOAD BTU

—7— HRVBBLVU1200 or HRVBBLVU1330 A98001 17 9⁄16″[446.9]4 3⁄4″[120.6]8 1⁄8″ DIA[206.4]2 PLCS 5 13⁄16″[147.6]5 7⁄8″ DIA[148.2] 2 PLCS6 15⁄16″[176.

Page 11 - +0.4 Btu

—8— PHYSICAL DATAPERFORMANCE DATAELECTRICAL DATA MODEL DESCRIPTION CONVENTIONAL COMPACT HIGH EFFICIENCYModel No. HRVBBVHU1150 HRVBBVHU1260 HRVBBSVC11

Page 12

—9— METHODS TO SIZE HRV’S METHOD 1 1. Calculate cu ft of occupied space.2. Multiply by recommended air changes per hr (AC/h).3. Divide by 60 minutes

Comments to this Manuals

No comments