Bryant 355CAV User Manual Page 50

  • Download
  • Add to my manuals
  • Print
  • Page
    / 62
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 49
50
The start up and shut down functions and delays described above
apply to the 2--stage medium/high heating mode as well, except for
switching from high-- to medium--heat.
1. Switching from High-- to Medium--Heat —Ifthe
thermostat R to W2 circuit opens, and the R to W1 circuit
remains closed, the furnace control CPU will gradually
decrease the inducer motor speed to the required
medium--heat RPM. When the inducer motor IDM reduces
pressure sufficiently, the high heat pressure switch HPS will
open and the high--heat gas valve solenoid GV--HI will be
de--energized. The gas valve solenoid GV--M will remain
energized as long as the low--heat pressure switch LPS
remains closed. When the inducer motor speed gets within
15% of the required medium--heat RPM the furnace control
CPU will start a 5 second blower airflow change delay.
After the 5 second blower airflow change delay is
completed the blower airflow will transition to
medium--heat airflow.
Cooling Mode
The thermostat “calls for cooling.”
2. Single--Speed Cooling
See Fig. 29 for thermostat connections.
The thermostat closes the R to G--and--Y circuits. The R to
Y circuit starts the outdoor unit, and the R to G--and--Y/Y2
circuits start the furnace blower motor BLWM on cooling
airflow. Cooling airflow is based on the A/C selection
shown in Fig. 47.
The electronic air cleaner terminal EAC--1 is energized with
115 vac when the blower motor BLWM is operating. When
the thermostat is satisfied, the R to G--and--Y circuits are
opened. The outdoor unit will stop, and the furnace blower
motor BLWM will continue operating at cooling airflow for
an additional 90 seconds. Jumper Y/Y2 to DHUM to reduce
the cooling off--delay to 5 seconds. (See Fig. 33.)
3. Single--Stage Thermostat and Two--Speed Cooling
(Adaptive Mode)
See Fig. 59 for thermostat connections.
This furnace can operate a two--speed cooling unit with a
single--stage thermostat because the furnace control CPU
includes a programmed adaptive sequence of controlled
operation, which selects low--cooling or high--cooling
operation. This selection is based upon the stored history of
the length of previous cooling period of the single--stage
thermostat.
NOTE: The air conditioning relay disable jumper ACRDJ must
be connected to enable the adaptive cooling mode in response to a
call for cooling. (See Fig. 33.) When in place the furnace control
CPU can turn on the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high--cooling.
The furnace control CPU can start up the cooling unit in either
low-- or high--cooling. If starting up in low--cooling, the furnace
control CPU determines the low--cooling on--time (from 0 to 20
minutes) which is permitted before switching to high--cooling.
If the power is interrupted, the stored history is erased and the
furnace control CPU will select low--cooling for up to 20 minutes
and then energize the air conditioning relay ACR to energize the
Y/Y2 terminal and switch the outdoor unit to high--cooling, as
long as the thermostat continues to call for cooling. Subsequent
selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the R to G and-- Y
circuits. The R to Y1 circuit starts the outdoor unit on low--cooling
speed, and the R to G--and--Y1 circuits starts the furnace blower
motor BLWM at low--cooling airflow which is the true on--board
CFselectionasshowninFig.47.
If the furnace control CPU switches from low--cooling to high
cooling, the furnace control CPU will energize the air conditioning
relay ACR. When the air conditioning relay ACR is energized the
R to Y1--and--Y2 circuits switch the outdoor unit to high--cooling
speed, and the R to G--and--Y1-- and--Y/Y2 circuits transition the
furnace blower motor BLWM to high--cooling airflow.
High--cooling airflow is based on the A/C selection shown in Fig.
47.
NOTE: When transitioning from low--cooling to high--cooling the
outdoor unit compressor will shut down for 1 minute while the
furnace blower motor BLWM transitions to run at high--cooling
airflow.
The electronic air cleaner terminal EAC--1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G--and--Y circuit are
opened. The outdoor unit stops, and the furnace blower BLWM
and electronic air cleaner terminal EAC--1 will remain energized
for an additional 90 seconds. Jumper Y1 to DHUM to reduce the
cooling off--delay to 5 seconds. (See Fig. 33.)
4. Two--Stage Thermostat and Two--Speed Cooling
See Fig. 58 for thermostat connections.
NOTE: The air conditioning relay disable jumper ACRDJ must
be disconnected to allow thermostat control of the outdoor unit
staging. (See Fig. 33.)
The thermostat closes the R to G--and--Y1 circuits for low cooling
or closes the R to G--and--Y1--and--Y2 circuits for high cooling.
The R to Y1 circuit starts the outdoor unit on low cooling speed,
and the R to G--and--Y1 circuit starts the furnace blower motor
BLWM at low--cooling airflow which is the true on--board CF
selection as shown in Fig. 47. The R to Y1--and--Y2 circuits start
the outdoor unit on high--cooling speed, and the R to G--and--Y/Y2
circuits start the furnace blower motor BLWM at high--cooling
airflow. High--cooling airflow is based on the A/C selection shown
in Fig. 47.
The electronic air cleaner terminal EAC--1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G--and--Y1 or R to
G--and--Y1--and--Y2 circuits are opened. The outdoor unit stops,
and the furnace blower BLWM and electronic air cleaner terminal
EAC--1 will remain energized for an additional 90 seconds. Jumper
Y1 to DHUM to reduce the cooling off--delay to 5 seconds. (See
Fig. 33.)
Thermidistat Mode
See Fig. 52--55 for thermostat connections.
The dehumidification output, DHUM on the Thermidistat should
be connected to the furnace control thermostat terminal DHUM.
When there is a dehumidify demand, the DHUM input is activated,
which means 24 vac signal is removed from the DHUM input
terminal. In other words, the DHUM input logic is reversed. The
DHUM input is turned ON when no dehumidify demand exists.
Once 24 vac is detected by the furnace control on the DHUM
input, the furnace control operates in Thermidistat mode. If the
DHUM input is low for more than 48 hours, the furnace control
reverts back to non--Thermidistat mode.
The cooling operation described above also applies to operation
with a Thermidistat. The exceptions are listed below:
1. Low cooling When the R to G--and--Y1 circuit is closed
and there is a demand for dehumidification, the furnace
blower motor BLWM will drop the blower airflow to 86%
of low cooling airflow which is the true on--board CF
selectionasshowninFig.47.
2. High cooling When the R to G--and Y/Y2 circuit is
closed and there is a demand for dehumidification, the
furnace blower motor BLWM will drop the blower airflow
to 86% of high--cooling airflow. High--cooling airflow is
basedontheA/CselectionshowninFig.47.
3. Cooling off--delay When the “call for cooling” is satisfied
and there is a demand for dehumidification, the cooling
355CAV
355CAV