IMPORTANT: Natural gas pressure at unit gas connection
must not be less than 5.5 in. wg or greater than 13.0 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas
connection.
IX. STEP 9 — MAKE ELECTRICAL CONNECTIONS
A. Field Power Supply
Unit is factory wired for voltage shown on unit nameplate.
Be sure to check for correct voltage.
When installing units, provide disconnect per NEC (National
Electrical Code) of adequate size (MOCP [Maximum Over-
current protection] of unit is on the informative plate). See
Tables 4A and 4B. All field wiring must comply with NEC
and local codes. Size wire based on MCA (Minimum Circuit
Amps) on the unit informative plate. See Fig. 15 for power
wiring connection to the unit power terminal block and
equipment ground.
Route power and ground lines through control box end panel
or unit basepan (see Fig. 4) to connections as shown on unit
wiring diagram and Fig. 15.
Field wiring must conform to temperature limitations for
type “T” wire. All field wiring must comply with NEC and
local requirements.
Operating voltage to compressor must be within voltage
range indicated on unit nameplate. On 3-phase units, volt-
ages between phases must be balanced within 2%.
Unit failure as a result of operation on improper line voltage
or excessive phase imbalance constitutes abuse and may
cause damage to electrical components.
B. Field Control Wiring
Unit must be controlled with a Bryant-approved accessory
thermostat. Install thermostat according to the installation
instructions included with accessory. Locate thermostat
assembly on a solid interior wall in the conditioned space to
sense average temperature.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through conduit into unit to
low-voltage connections as shown on unit label wiring dia-
gram and in Fig. 16.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directly connected at
the thermostat and will require a junction box and splice at
the thermostat.
WARNING: Do not pressure test gas supply while
connected to unit. Always disconnect union before ser-
vicing. A hazardous condition could occur resulting in
serious injury.
CAUTION: The correct power phasing is critical to
the operation of the scroll compressors. An incorrect
phasing will result in compressor shutdown on thermal
overload and possible damage to compressor. Should
this occur, power phase correction must be made to the
incoming power.
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the
possibility of personal injury if an electrical fault
should occur. This ground may consist of electrical wire
connected to unit ground lug in control compartment,
or conduit approved for electrical ground when
installed in accordance with NEC, ANSI/NFPA
(National Fire Protection Association), latest edition,
and local electrical codes. Do not use gas piping as an
electrical ground. Failure to follow this warning could
result in the installer being liable for personal injury of
others.
Fig. 12 — Condensate Drain Details
Fig. 14 — Field Gas Piping
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
Fig. 13 — Condensate Drain Piping Details