IMPORTANT — READ BEFORE INSTALLING
1. This installation instruction is intended for use ONLY
ON units with 3 outdoor fans.
2. Read and become familiar with installation instruc-
tions before installing accessory single-phase, variable
speed head pressure controller.
3. Be sure the installation conforms to all local and na-
tional codes.
4. Open, lock, and tag unit electrical disconnect switch be-
fore installing head pressure controller.
PACKAGE CONTENTS
ITEM QUANTITY
Head Pressure Control Assembly
with Attached Sensor Assembly
1
No. 10 Sheet Metal Screw 4
Star Lockwasher 4
3
⁄
4
-in. Lg, 4-40 Screw 2
Plate Washer 2
4-40 Nut 2
Wirenut 2
NOTE: The 208/230-v head pressure control device is rated at 8 amps
(307183-101), and the 460-v head pressure control device is rated at
4 amps (307183-102).
SAFETY CONSIDERATIONS
Installation, start-up, and servicing of this equipment can be
hazardous due to system pressures, electrical components, mov-
ing parts, and equipment location.
Only trained, qualified installers and service mechanics should
install, start up, and service this equipment. Untrained per-
sonnel can perform such basic maintenance functions as clean-
ing coils or replacing air filters. All other operations should
be performed by trained service personnel only.
When working on equipment, observe precautions in litera-
ture; tags, stickers, and labels attached to equipment; and
any other safety precautions that apply. Follow all safety codes,
and wear safety glasses and work gloves. Use care in han-
dling, rigging, and setting bulky equipment.
WARNING:
Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit. Electrical shock could result in personal injury.
INTRODUCTION
IMPORTANT: This installation instruction is intended for use
ONLY ON units with 3 outdoor fans.
The solid-state head pressure control is a fan speed control
device actuated by a temperature sensor. It is specifically de-
signed for use on Bryant, Day & Night, and Payne equip-
ment and controls the outdoor-fan motor speed in response
to the saturated condensing temperature. For outdoor
temperatures down to −20 F, it maintains condensing tem-
perature at 100 F 610 F.
On units with 3 outdoor fans, the head pressure controller
must be used in conjunction with the accessory 0° F low-
ambient kit (part no. 389221-701 on 551A, 559F, 579F, 581A
units; part no. CRLOWAMB001A00 on 542J units). The head
pressure control device controls outdoor-fan motor no. 1 (see
Fig. 1) while condenser-fan motors no. 2 and no. 3 are se-
quenced off by the temperature switches in the accessory
0° F low-ambient kit.
IMPORTANT: All units must be modified for winter start con-
trol. See instructions included with the accessory winter start
control for more details.
OFM — Outdoor-Fan Motors
Fig. 1 — Outdoor Fans and Motormaster I
Controller Locations
installation instructions
ACCESSORY MOTORMASTERT I
HEAD PRESSURE CONTROLLER
P/N 307183-101 AND 307183-102
542J150,180
551A/581A155,180
559F/579F180,216
Cancels: IIK 551A-155-1 IIK 542J-150-2
6/15/96