Bryant 548F User Manual Page 31

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 30
31
Table 21 Fan Performance, 548F036 High-Static Motor Horizontal Discharge Units
LEGEND
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-
supplied drive.
NOTES:
1.
Boldface
indicates field-supplied drive is required.
2. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
3. Maximum continuous bhp is 2.4 and the maximum continuous watts
are 2120. Extensive motor and electrical testing on these units
ensures that the full range of the motor can be utilized with confi-
dence. Using your fan motors up to the wattage ratings shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected. See Indoor-Fan Motor Performance,
Table 6 for additional information.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
5. Interpolation is permissible. Do not extrapolate.
Table 22 Fan Performance, 548F048 Standard Motor Horizontal Discharge Units
LEGEND
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
Table 7 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not
be affected. For additional information on motor performance, refer
to Indoor-Fan Motor Performance, Table 6.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
548F036 (3 TONS) HIGH-STATIC MOTOR (BELT DRIVE)*
Airflow
(Cfm)
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
900 584 0.08 99 734 0.22 219 875 0.27 269 953 0.35 348 1028 0.42 438
1000 627 0.13 149 800 0.26 259 895 0.31 308 977 0.39 388 1064 0.48 477
1100 670 0.16 189 812 0.29 288 914 0.35 348 1005 0.43 428
1100 0.52 527
1200 710 0.23 229 840 0.32 318 938 0.40 398 1038 0.50 497
1136 0.59 577
1300 752 0.27 269 868 0.37 368 963 0.45 448 1061 0.56 557
1172 0.65 647
1400 776 0.31 308 891 0.42 418 983 0.51 507 1071 0.60 597
1208 0.70 706
1500 816 0.38 378 924 0.48 477 1014 0.58 577
1097 0.68 676 1245 0.74 776
548F036 (3 TONS) HIGH-STATIC MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
External Static Pressure (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
900
1120 0.54 537 1155 0.59 589 1186 0.64 639 1215 0.69 685 1240 0.73 730
1000
1185 0.60 597 1222 0.66 655 1255 0.71 709 1285 0.77 761 1312 0.82 811
1100
1225 0.65 647 1263 0.71 709 1298 0.77 769 1328 0.83 825 1357 0.88 879
1200
1266 0.72 716 1306 0.79 786 1341 0.86 851 1373 0.92 914 1402 0.98 973
1300
1306 0.79 786 1347 0.87 862 1383 0.94 934 1416 1.01 1003 1446 1.07 1068
1400
1347 0.87 865 1389 0.95 950 1427 1.03 1029
1461 1.11 1104 1492 1.18 1176
1500
1385 0.96 955 1428 1.05 1048
1467 1.14 1135 1502 1.22 1218 1534 1.30 1298
Bhp
Brake Horsepower Input to Fan
FIOP
Factory-Installed Option
Watts
Input Watts to Motor
548F048 (4 TONS) STANDARD MOTOR (DIRECT DRIVE)
Airflow
(Cfm)
Low Speed High Speed
208 v 230, 460, 575 v 208 v 230, 460, 575 v
ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts ESP Bhp Watts
1200
0.93 0.41 458 0.97 0.45 506 1.04 0.51 572 1.09 0.56 632
1300
0.86 0.42 471 0.90 0.46 521 0.96 0.52 589 1.02 0.58 651
1400
0.78 0.45 503 0.84 0.49 556 0.90 0.54 616 0.96 0.60 681
1500
0.73 0.47 536 0.76 0.52 593 0.83 0.56 631 0.89 0.62 698
1600
0.67 0.49 557 0.70 0.54 616 0.75 0.58 654 0.82 0.64 723
1700
0.60 0.52 584 0.63 0.57 646 0.67 0.60 678 0.74 0.66 750
1800
0.51 0.54 610 0.54 0.60 674 0.62 0.62 698 0.69 0.68 772
1900
0.40 0.56 629 0.45 0.62 696 0.54 0.64 720 0.62 0.70 796
2000
0.32 0.58 661 0.33 0.65 731 0.47 0.66 744 0.54 0.73 823
Bhp
Brake Horsepower Input to Fan
ESP
External Static Pressure (in. wg)
FIOP
Factory-Installed Option
Watts
Input Watts to Motor
Page view 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 47 48

Comments to this Manuals

No comments