Bryant 548F User Manual Page 39

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 38
39
the first stage of cooling is satisfied, there is a 30-second delay
before the evaporator fan shuts off. The damper then moves to
the fully closed position. When using a continuous fan, the
damper moves to the minimum position.
E. Heating, Units With Economizer
Upon a call for heat through W1, the IFC energizes to start
the evaporator fan and the economizer damper blade opens
to the minimum position. If the accessory two-position
damper is used, the outdoor-air damper opens to the mini-
mum position whenever the evaporator fan runs. If unit is
equipped with 2 stages of heat, when additional heat is
needed a call is made through W2.
As space temperature approaches the heating temperature
set point, heating stages cycle off. Economizer or two-posi-
tion damper returns to fully closed position.
F. D e f rost
As frost builds up on the outdoor coil, the coil temperature
drops below 28 F. When this outdoor-coil temperature drop is
sensed by the defrost thermostat (DFT) and the defrost timer
is at the end of a timed period (adjustable at 30, 50, or 90
minutes), the unit operates in a defrost cycle controlled by the
defrost timer and thermostat. During this cycle, the reversing
valve solenoid (RVS) is energized and the outdoor fan shuts
off. The electric heaters (if installed) will be energized.
The unit continues to defrost until the coil temperature as
measured by DFT reaches 65 F, or the duration of defrost
cycle completes a 10-minute period.
At the end of the defrost cycle, the electric heaters (if
installed) and the reversing valve will be deenergized, and
the outdoor-fan motor will be energized. The unit will now
operate in the Heating mode.
If the thermostat is satisfied during a defrost cycle, the unit
will continue in the Defrost mode until the time or tempera-
ture constraints are satisfied.
SERVICE
I. CLEANING
Inspect unit interior at the beginning of each heating and
cooling season and as operating conditions require.
A. Indoor Coil
1. Turn unit power off and tag disconnect. Remove filter
access panel and indoor coil access panel.
2. If accessory economizer is installed, remove econo-
mizer by disconnecting Molex plug and removing
economizer mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish-
washer detergent in a pressurized spray canister.
Wash both sides of coil and flush with clean water.
For best results, back-flush toward return-air section
to remove foreign material. Flush condensate pan
after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
B. Outdoor Coil
Inspect coil monthly. Clean outdoor coil annually, and as
required by location or outdoor-air conditions.
One-Row Coils
— Wash coil with commercial coil cleaner. It
is not necessary to remove top panel.
2-Row Coils — Clean coil as follows:
1. Turn off unit power and tag disconnect.
2. Remove top panel screws on outdoor end of unit.
3. Remove outdoor coil corner post. See Fig. 35. To hold
top panel open, place coil corner post between top
panel and center post. See Fig. 36.
4. Remove device holding coil sections together at
return end of outdoor coil. Carefully separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 37.
5. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
6. Secure the sections together. Reposition the outer coil
section, and remove the coil corner post from between
the top panel and center post. Install the coil corner
and center posts, and replace all screws.
C. Condensate Drain
Check and clean each year at start of cooling season. In win-
ter, keep drain dry or protect against freeze-up.
D. Filters
Clean or replace at start of each heating and cooling season,
or more often if operating conditions require it. Replacement
filters must be same dimensions as original filters.
E. Outdoor-Air Inlet Screens
Clean screens with steam or hot water and a mild detergent.
Do not use disposable filters in place of screens.
II. LUBRICATION
A. Compressor
The compressor is charged with the correct amount of oil at
the factory.
B. Fan Motor Bearings
Fan motor bearings are permanently lubricated. No further
lubrication of outdoor- or indoor-fan motors is required.
III. OUTDOOR-FAN ADJUSTMENT (FIG. 38)
1. Shut off unit power supply and tag disconnect.
2. Remove outdoor-fan assembly (grille, motor, motor
cover, and fan) by removing screws and flipping
assembly onto unit top cover.
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 38.
5. Tighten setscrews.
6. Replace outdoor-fan assembly.
IV. BLOWER BELT ADJUSTMENT
Inspect blower belt for wear, proper belt tension, and pulley
alignment as conditions require or at the beginning of each
heating and air conditioning season. Refer to Step 7 —
Adjust Evaporator Fan Speed on page 20 for adjustment and
alignment procedure.
V. ECONOMIZER ADJUSTMENT
Refer to Optional Economizer sections on pages 13 and 16.
VI. HIGH-PRESSURE SWITCH
Located on the compressor hot gas line is a high-pressure
switch containing a Schrader core depressor. This switch
opens at 428 psig and closes at 320 psig. No adjustment is
necessary. Refer to Table 1.
CAUTION:
Page view 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 47 48

Comments to this Manuals

No comments