Table 35 — EconoMi$er+ Inputs and Outputs
*If there are 3 stages then there can only be 1 stage of power exhaust.
†If there are 4 stages then no power exhaust stages are directly controlled.
INPUT NAME TYPE USE
INPUT/OUTPUT
RANGE
CONVERSION
RANGE
CONVERSION
RESOLUTION
CONNECTION
PIN
NO.
THERMOSTAT INPUTS
Y1 (Cool/Low Cool) Y1 Switch Standard 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 1
Y2 (Cool 2/High Cool) Y2 Switch Option 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 2
G (fan) G Switch Standard 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 3
Occupied/Unoccupied OCC Switch Option 18-30 vac 50/60 Hz w/min 24 mA Load NA On/Off J1 4,5
POWER
Power 24V Input Standard 18-30 VAC 50/60 Hz NA NA J2 1,2
ECONOMIZER MOTOR
Control CNT 2-10 vdc Standard 2-10 vdc 0-100% 1% J2 3,4,5
ANALOG INPUTS
Supply Air Temperature SAT 10 K Thermistor Standard 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 1,2
Outside Air
Temperature
OAT 10 K Thermistor Standard 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 3,4
Return Air Temperature RAT 10 K Thermistor Option 1816 to 86407 Ohms 30 to 125 F 0.8 F J3 5,6
Indoor Humidity IRH
4-20 mA,
Loop Powered
Option 4-20 mA, 24 vdc 0-100% .08 mA J3 7,8,9
Outdoor Humidity ORH
4-20 mA,
Loop Powered
Option 4-20 mA, 24 vdc 0-100% .08 mA J3
10,11,1
2
Indoor CO
2
IAQ
4-20 mA,
Ext Sourced
Option 4-20 mA, 24 vdc 0-200 PPM/10 10 PPM J3 13,14
Remote Minimum
Position Pot
MIN 10K Option 10K to 100K Ohms 0 to 100% 1% J3
15,16,1
7
RELAY OUTPUTS
Cooling Stage 1 CP1 Relay Standard 24 vac, 2.5 Amps at 24 vac NA On/Off J4 1,3,4
Cooling Stage 2 CP2 Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 2,3,4
Power Exhaust 2/
Cooling Stage 3*
CP3/
EX2
Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 5,6
Power Exhaust 1/
Cooling Stage 4
CP4/
EX1
Relay Option 24 vac, 2.5 Amps at 24 vac NA On/Off J4 5,7
DISPLAY
Setpoint Switch 1 SP1 Digital Standard Open/Closed Logic Open/Closed On Board NA
Setpoint Switch 2 SP2 Digital Standard Open/Closed Logic Open/Closed On Board NA
LED 1 DS1 LED Output Standard Red Logic On/Off On Board NA
LED 2 DS2 LED Output Standard Yellow Logic On/Off On Board NA
LED 3 DS3 LED Output Standard Green Logic On/Off On Board NA
LED 4 DS4 LED Output Standard Green Logic On/Off On Board NA
Y1
Y2
G
OCC
24V
1
J1
5
Y1 (cool 1)
Y2 (cool 2)
G (fan)
OCC
24 VAC
THERMOSTAT INPUTS
Occupied/unoccupied
I/O support dry circuit
contact (min 24 mA I)
POWER
SUPPLY
2-10 VDC
ECONOMIZER
CONTROL
J2
1
5
CNT
24V
24V
24 VAC
24 VAC
Control
SAT
OAT
RAT
IRH
VRF
ORH
VRF
IAQ
MIN
VRF
IAQ (4-20ma)
min (10K pot)
ORH (4-20 ma)
Vref
Vref
Vref
IRH (4-20 ma)
RAT (10k thermistor)
OAT (10k thermistor)
SAT (10k thermistor)
J3
1
17
ANALOG INPUTS
4-20 mA external powered between signal and ground
4-20 mA loop powered between 24 VDC and signal
Relays rated at 24 VAC 3A
and traces for 8A.
NOTE: For 1 and 2 stage
cooling, 2 stages of power
exhaust will be used.
For 3 cooling stages, only 1
stage of power exhaust will be
used, and for 4 stages no power
exhaust will be controlled
directly by the control.
OUTPUT RELAYS
C1
C2
24V
24V
24V
C3
C4
24 VAC
24 VAC
24 VAC
CP1
CP2
EX2/CP3
EX1/CP4
J4
READ/
ADJUST
ADVANCE
MANUAL
DS1 DS2
SETPOINT DISPLAY
DS3
DS4
date or serial no
RED
YELLOW
GREEN
PUSH BUTTONS
#1
#2
Fig. 36 — EconoMi$er+ Controller Board