Bryant 580J*04--12 Installation Manual

Browse online or download Installation Manual for Split-system air conditioners Bryant 580J*04--12. Bryant 580J*04--12 Unit installation User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
580J/558J*04--30, 548J*04--24
581J/551J*04--28, 549J*04--12
Factory Installed Option
RTU Open
Controls, Start--Up, Operation,
and Troubleshooting
TABLE OF CONTENTS
SAFETY CONSIDERATIONS 2.........................
GENERAL 2.........................................
SENSOR/ACCESSORY INSTALLATION 2................
Sensors and Accessories 4.............................
User Interface 4......................................
Install Analog Sensors 4...............................
Supply Air Sensor (SAT) 4...........................
Outdoor Air Sensor (OAT) 4..........................
Space Temperature Sensor (SPT) 4.....................
Sensor Averaging 8.................................
CO
2
Sensor(s) (IAQ and OAQ) 8......................
Relative Humidity Sensors (Space or Duct Mounted) 10.....
Installing Discrete Inputs 10............................
Compressor Safety 10...............................
Humidistat 10.....................................
Single Enthalpy (Outdoor Enthalpy) 10.................
Differential Enthalpy 10.............................
Fire Shutdown 11..................................
Filter Status 11.....................................
Fan Status 11......................................
Remote Occupancy 11...............................
Communication Wiring--Protocols 12.....................
General 12........................................
BACnet
R
MS/TP 12................................
Modbus 13.......................................
Johnson N2 13.....................................
LonWorks 13......................................
Local Access 14....................................
START--UP 15........................................
Additional Installation/Inspection 15.....................
Power Exhaust Relay Power 15........................
Service Test 15......................................
Fan Test 15.......................................
High Speed Fan Test 15..............................
Compressor 1 and Compressor 2 Test 15.................
Heat 1 and Heat 2 Test 15............................
Dehumidification Test 15.............................
Power Exhaust Test 16..............................
Economizer Test 16.................................
VFD Speed Test 16.................................
Configuration 16....................................
Setpoint 16.......................................
Unit 16..........................................
Inputs 17.........................................
Service Configuration 18.............................
OPERATION 19......................................
Occupancy 19.......................................
Indoor (Supply) Fan 20...............................
Cooling 20.........................................
Supply Fan 21......................................
Economizer 21......................................
Enthalpy Control 21..................................
Space Air Quality 22.................................
Power Exhaust 22....................................
Pre--Occupancy Purge 22..............................
Heating 22.........................................
Indoor Air Quality 22.................................
Dehumidification 23..................................
Demand Limit 23....................................
Unoccupied Free Cooling 23...........................
Optimal Start 23.....................................
Fire Shutdown 23....................................
Compressor Safety 23.................................
Fan Status 23.......................................
Filter Status 24......................................
Door Switch 24......................................
Remote Occupancy 24................................
TROUBLESHOOTING 24..............................
General 24.........................................
Replacing the RTU Open’s Battery 24...................
Thermistor Troubleshooting 24.........................
Software Version 25..................................
Communication LED’s 25.............................
Alarms 28..........................................
Performance 30......................................
Third Party Networking 31.............................
APPENDIX A -- USER INTERFACE MENUS 33............
APPENDIX B -- THIRD PARTY POINTS LIST 40..........
RTUOPENSTART--UPSHEET 44.......................
Page view 0
1 2 3 4 5 6 ... 47 48

Summary of Contents

Page 1 - TABLE OF CONTENTS

580J/558J*04--30, 548J*04--24581J/551J*04--28, 549J*04--12Factory Installed OptionRTU OpenControls, Start--Up, Operation,and TroubleshootingTABLE OF C

Page 2

10Relative Humidity Sensors (Space or DuctMounted)The accessory space humidity sensor or duct humiditysensor is used to measure the relative humidity

Page 3

11SPANZERO4-20mAVACorVDCGND 0-5Vor0-10V123456ONJ4-1 or J4-4 + 24 VDC Supply VoltageJ4-2 or J4-5 (-)4 to 20 mA Current Loop Outputto RTU OpenRelative H

Page 4 - Install Analog Sensors

12C10821Fig. 12 -- Enthalpy Switch and Sensor WiringCommunication Wiring--ProtocolsGeneralProtocols are the communication languages spoken bycontrol d

Page 5

13SW3 Protocol SelectionPROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1BACnet MS/TP(Master)Unused OFF OFF OFF ON OFF Select Baud Select BaudModbus(Slave)Unus

Page 6

14LON OC Rev.4Net1 2J15COMMOPTIONNetworkConnectorC12750Fig. 16 -- LON--OC and LON Network WiringLocal AccessField AssistantField Assistant is a comput

Page 7

15START--UPIMPORTANT: Follow the base unit’s start-up sequencedocumented in its specific instructions. Use the base unit’sstart-up check list when per

Page 8 - CO2 Sensor(s) (IAQ and OAQ)

16Power Exhaust TestThis point allows the board’s power exhaust (PE) outputto be manually turned On (Enable) and Off (Disable).Power Exhaust test can

Page 9 - To controller

17DCV Max Vent Damper Pos – This is the greatestposition the economizer can open to while trying tocontrol the indoor air quality levelsRange = 0 -- 7

Page 10 - Installing Discrete Inputs

18Input 5 -- This input is a discrete input and can beconfigured to be one of six different functions: No Function,Fire Shutdown, Fan Status, Filter S

Page 11 - Remote Occupancy

19Number of Heat Stages – Indicates how many heatstages are available for use. See configuration inAppendix A for details on specific unit configurati

Page 12 - TS---5580J---02

2SAFETY CONSIDERATIONSInstallation and servicing of air-conditioning equipmentcan be hazardous due to system pressure and electricalcomponents. Only t

Page 13 - LonWorks

20switch input. Inputs 3, 5, 8, and 9 on plug J5 can behard-wired to command the unit’s occupancy. TheOccupancy Contact point show the status as on or

Page 14 - Local Access

21Supply FanThe RTU Open supply fan may be configured for 1 of 3Fan Control modes:S Single -- The fan operates at one speed only andprovides on/off op

Page 15 - START--UP

22Enthalpy Status that is Low enables the economizer if a callfor cooling exists and the remaining preconditions are met.Space Air QualitySpace Air Qu

Page 16 - Configuration

23value becomes the final minimum damper position of theeconomizer output.If the IAQ minimum position calculated by the control isgreater than the DCV

Page 17

24Filter StatusFilter status may be configured on any unused binary inputchannel. A typical application is a differential pressureswitch that senses t

Page 18 - Service Configuration

25Software VersionDuring Start-up and throughout the life of the equipment,it may be necessary to obtain the RTU Open’s softwareversion. To do this a

Page 19 - OPERATION

26Table 3 – LED’sThe LED’s on the RTU Open show the status of certain functionsIf this LED is on... Status is...Power The RTU Open has powerRx The RTU

Page 20 - Indoor (Supply) Fan

27Table 4 -- RTU Open Alarms (cont)POINT NAMEBACnet ObjectNAMEACTION TAKEN BYCONTROLRESET METHOD PROBABLE CAUSEIndoor Air Quality Sen sor iaq_sensor_f

Page 21 - Enthalpy Control

28AlarmsAlarms are provided to indicate a possible problem withthe controller or unit. Alarms can be checked through anetwork and/or the local access

Page 22 - Indoor Air Quality

29OAQ SensorThis alarm indicates the mA input at the associatedchannel falls below 3.5 mA or rises above 21 mA, or theNetwork value for space RH is no

Page 23

3J4J2J1J5 J5J22J17J19J14J11J22J3J13J12J15J20Network CommConfigurable - Input_824 VACConfigurable - Input_524 VACConfigurable - Input_324 VACInput_9 (H

Page 24 - TROUBLESHOOTING

30PerformanceCurrent Performance DataThe RTU Open collects performance data duringoperation. The data can be used to monitor the operationof the unit

Page 25 - Communication LED’s

31Heating UtilizationThe value of the Heating Utilization when the currentperformance data was last reset.Previous High OATThe value of the Recorded H

Page 26 - Table4–RTUOpenAlarms

32APPENDIX A -- USER INTERFACE MENUSField Assistant NavigationPropertiesControl ProgramStatusConfigurationUnit ConfigurationSetpointsAlarm Configurati

Page 27

33APPENDIX A -- USER INTERFACE MENUS (CON’T)Field Assistant MenuAccessLevel3=ADMIN2=USER1=No PWPOINT NAME BACnet Object RANGE DEFAULTSTATUSProperties&

Page 28

34APPENDIX A -- USER INTERFACE MENUS (CON’T)Field Assistant MenuAccessLevel3=ADMIN2=USER1=No PWPOINT NAME BACnet Object RANGE DEFAULTINPUT CONFIGURATI

Page 29

35APPENDIX A -- USER INTERFACE MENUS (CON’T)Field Assistant MenuAccessLevel3=ADMIN2=USER1=No PWPOINT NAME BACnet Object RANGE DEFAULTSETPOINTPropertie

Page 30 - Performance

36APPENDIX A -- USER INTERFACE MENUS (CON’T)Field Assistant MenuAccessLevel3=ADMIN2=USER1=No PWPOINT NAME BACnet Object RANGE DEFAULTSERVICE CONFIGURA

Page 31 - Third Party Networking

37APPENDIX A -- USER INTERFACE MENUS (CON’T)Field Assistant MenuAccessLevel3=ADMIN2=USER1=No PWPOINT NAME BACnet Object RANGE DEFAULTSERVICE TESTPrope

Page 32 - Control Program

38APPENDIX A -- USER INTERFACE MENUS (CON’T)Field Assistant MenuAccessLevel3=ADMIN2=USER1=No PWPOINT NAME BACnet Object RANGE DEFAULTOCCUPANCY (MAINTE

Page 33

39APPENDIX A -- USER INTERFACE MENUS (CON’T)Field Assistant MenuAccessLevel3=ADMIN2=USER1=No PWPOINT NAME BACnet Object RANGE DEFAULTALARMSProperties&

Page 34

4Table 1 – RTU Open Inputs and OutputsPOINT NAMEBACnet OBJECTNAMETYPE OF I/OCONNECTION PINNUMBER(S)CHANNEL DESIGNATIONDEDICATED INPUTSSpace Temp / Zon

Page 35

40APPENDIX B -- THIRD PARTY POINTS LISTRTU Open Protocol MapsPoint NamePointAccessUnitsBACnet Info Modbus Info N2 Info LonWorks InfoBACnetPoint NameBA

Page 36

41APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)RTU Open Protocol MapsPoint NamePointAccessUnitsBACnet Info Modbus Info N2 Info LonWorks InfoBACnetPoin

Page 37

42APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)RTU Open Protocol MapsPoint NamePointAccessUnitsBACnet Info Modbus Info N2 Info LonWorks InfoBACnetPoin

Page 38

43APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)RTU Open Protocol MapsPoint NamePointAccessUnitsBACnet Info Modbus Info N2 Info LonWorks InfoBACnetPoin

Page 39

44RTUOPENSTART--UPSHEETRTU Model Number: Date:RTU Serial Number:Performed by:RTU Open Software Version: Company:Protocol and Baud Rate: Network Addres

Page 40 - RTU Open Protocol Maps

45CONFIGURATION POINTS (CON’T)POINT NAME BACnet Object RANGE DEFAULT ENTRYUNIT CONFIGURATIONFan Mode fan_mode 1=Auto2=Continuous3=Always OnContinuousP

Page 41

46CONFIGURATION POINTS (CON’T)POINT NAME BACnet Object RANGE DEFAULT ENTRYINPUT CONFIGURATIONInput 1 Function ai1_function 1=No Sensor2=IAO Sensor3=OA

Page 42

47CONFIGURATION POINTS (CON’T)POINT NAME BACnet Object RANGE DEFAULT ENTRYSERVICE CONFIGURATIONUnit Type unit_type 1=Heat/Cool2=n/a3=HP O/B Ctrl4=HP Y

Page 43 - Catalog No: TS---5580J---02

482014 Bryant Heating & Cooling Systems. D 7310 W. Morris St. D Indi anapolis, IN 46231 Edition Date: 06/14Manufacturer reser ves the right to ch

Page 44 - CONFIGURATION POINTS

5C14179Fig. 2 -- Typical Factory Option Wiring -- 580J 04--07 ShownTS---5580J---02

Page 45 - CONFIGURATION POINTS (CON’T)

6C13768Fig. 3 -- Typical Factory Option Wiring -- 580J 17--30 ShownTS---5580J---02

Page 46

7C13668Fig. 4 -- Typical Factory Option Wiring -- 551J 17--28 ShownTS---5580J---02

Page 47

8Resistive Non--Communicating Sensor WiringFor sensor with setpoint adjustment up to 1000 ft (305m),use three-conductor shielded cable 20 gauge wire t

Page 48

9Combination Temperature and CO2SensorIf using a combination temperature and CO2sensor(33ZCT55CO2--02 or 33ZCT56CO2--02), refer to theinstallation ins

Comments to this Manuals

No comments