TABLE 4A
Tier 1 (effective January 1, 2010) SRE and minimum
fan efficacy requirements
Minimum Minimum Minimum fan efficacy with 0°C
SRE at 0°C SRE at -25°C (32°F) supply temperature
(32°F) (-13°F)
SRE < 75% 1 cfm/W
60% 55%
(0.47 L/s/W)
SRE 75% any cfm/W
(L/s/W)
TABLE 4B
Tier 2 (effective July 1, 2012) SRE and minimum fan
efficacy requirements
Minimum Minimum Minimum fan efficacy with 0°C
SRE at 0°C SRE at -25°C (32°F) supply temperature
(32°F) (-13°F)
SRE < 75% 1.2 cfm/W
65% 60%
(0.57 L/s/W)
SRE 75% 0.8 cfm/W
(0.38 L/s/W)
For a list of ENERGY STAR qualified HRVs and ERVs, visit
oee.nrcan.gc.ca/equipment/heating/13082.
SRE = sensible heat-recovery efficiency
cfm = cubic feet per minute
L/s = litres per second
W = watt