2. Clear the exterior intake and exhaust vents of obstructions. Check the
outside vents regularly to ensure that the screen openings are not
obstructed by grass, bushes, leaves or other debris (see Figure 6).
Do not replace the screen with mesh smaller than ¼ inch because
it will block airflow. If the exhaust hood has a back-draft damper,
check it for free operation and proper positioning (the damper
should be closed when there is no airflow).
You might want to check the hoods more often in the autumn
(when there are leaves on the ground) and during the winter (to
ensure that snow or frost build-up does not block the openings).
Over time, you will become the best judge of how frequently
you should check your HRV hoods. If the openings are regularly
clogged or blocked, consider having the vent openings moved
higher up the wall.
3. Clean the heat-exchange core. Inspect the heat-exchange core
twice a year and clean it as required (consult your owners
manual for instructions on inspecting and cleaning the core).
A build-up of dust and dirt can restrict airflow and reduce the
efficiency of your HRV. After inspection and cleaning, make
sure the core is replaced right-side-up. It is also a good idea
to inspect the heat exchange core during very cold weather to
ensure that the defrost mechanism is working.
4. Clean the condensate drain and pan. Twice a year, check the
condensate drain (if your HRV has one) and tubing to ensure that
they are open and free-flowing. To do this, find the hole that leads
to the drain inside the unit. Then pour two or three litres of warm
water into the pan leading to the drain. If the water does not flow
freely, unblock the drain using a piece of thin wire. The tubing
can be disconnected for cleaning. The condensate drain must
have a “trap” – an S or loop in the tubing that traps a quantity of
water – to prevent air from entering the HRV through this tubing
(see Figure 1, page 9).
You should also clean the condensate pan, located inside
the HRV.