Bryant LEGACY 213R Service Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
12
Capacitor
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or equipment damage.
Capacitors can store electrical energy when power is off.
Electrical shock can result if you touch the capacitor
terminals and discharge the stored energy. Exercise extreme
caution when working near capacitors. With power off,
discharge stored energy by shorting across the capacitor
terminals with a 15,000--ohm, 2-- watt resistor.
!
WARNING
NOTE: If bleed resistor is wired across start capacitor, it must be
disconnected to avoid erroneous readings when ohmmeter is
applied across capacitor. (S)
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or equipment damage.
Always check capacitors with power off. Attempting to
troubleshoot a capacitor with power on can be dangerous.
Defective capacitors may explode when power is applied.
Insulating fluid inside is combustible and may ignite,
causing burns.
!
WARNING
Capacitors are used as a phase--shifting device to aid in starting
certain single--phase motors. Check capacitors as follows:
1. With power off, discharge capacitors as outlined above.
Disconnect capacitor from circuit. Put ohmmeter on R X
10k scale. Using an analog ohmmeter, check each terminal
to ground (use capacitor case). Discard any capacitor which
measures 1/2 scale deflection or less. Place ohmmeter leads
across capacitor and place on R X 10k scale. Meter should
jump to a low resistance value and slowly climb to higher
value. Failure of meter to do this indicates an open
capacitor. If resistance stays at 0 or a low value, capacitor is
internally shorted.
2. Capacitance testers are available which will read value of
capacitor. If value is not within ±10 percent value stated on
capacitor, it should be replaced. If capacitor is not open or
shorted, the capacitance value is calculated by measuring
voltage across capacitor and current it draws.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Exercise extreme caution when taking readings while power
is on.
!
WARNING
Use following formula to calculate capacitance:
Capacitance (mfd)= (2650 X amps)/volts
3. Remove any capacitor that shows signs of bulging, dents, or
leaking. Do not apply power to a defective capacitor as it
may explode.
Sometimes under adverse conditions, a standard run capacitor in a
system is inadequate to start compressor. In these instances, a start
assist device is used to provide an extra starting boost to
compressor motor. This device is called a positive temperature
coefficient (PTC) or start thermistor. It is a resistor wired in parallel
with the run capacitor. As current flows through the PTC at
start--up, it heats up. As PTC heats up, its resistance increases
greatly until it effectively lowers the current through itself to an
extremely low value. This, in effect, removes the PTC from the
circuit.
After system shutdown, resistor cools and resistance value returns
to normal until next time system starts. Thermistor device is
adequate for most conditions, however, in systems where off cycle
is short, device cannot fully cool and becomes less effective as a
start device. It is an easy device to troubleshoot. Shut off all power
to system.
Check thermistor with ohmmeter as described below. Shut off all
power to unit. Remove PTC from unit. Wait at least 10 minutes for
PTC to cool to ambient temperature.
Measure resistance of PTC with ohmmeter.
The cold resistance (RT) of any PTC device should be
approximately 100--180 percent of device ohm rating.
12.5--ohm PTC = 12.5--22.5 ohm resistance (beige color)
If PTC resistance is appreciably less than rating or more than 200
percent higher than rating, device is defective.
A94006
Fig. 6 Capacitors
Cycle Protector
Bryant thermostats have anti--cycle protection built in to protect the
compressor. Should a non --Bryant stat be utilized, it is
recommended to add a cycle protector to the system. Solid-- state
cycle protector protects unit compressor by preventing short
cycling. After a system shutdown, cycle protector provides for a 5
± 2-- minute delay before compressor restarts. On normal start-- up, a
5--minute delay occurs before thermostat closes. After thermostat
closes, cycle protector device provides a 3 -- sec delay.
Cycle protector is simple to troubleshoot. Only a voltmeter capable
of reading 24v is needed. Device is in control circuit, therefore,
troubleshooting is safe with control power (24v) on and
high--voltage power off.
With high -- voltage power off, attach voltmeter leads across T1 and
T3, and set thermostat so that Y terminal is energized. Make sure
all protective devices in series with Y terminal are closed.
Voltmeter should read 24v across T1 and T3. With 24v still
applied, move voltmeter leads to T2 and T3. After 5 ± 2 minutes,
voltmeter should read 24v, indicating control is functioning
normally. If no time delay is encountered or device never times out,
change control.
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 65 66

Comments to this Manuals

No comments