ACCESSORIES
Table 1—Required Field--Installed Accessories for Air Conditioners
Accessory
REQUIRED FOR LOW---AMBIENT
COOLING APPLICATIONS
(Below 55°F / 12.8°C)
REQUIRED FOR LONG LINE
APPLICATIONS* (Over 80 ft. / 24.38 m)
Crankcase Heater Ye s
Yes
Compressor Start Assist Capacitor and Relay Ye s Ye s
Evaporator Freeze Thermostat
Ye s
(For non ---Evolution systems only)
No
Liquid Line Solenoid Valve No
See Long---Line Application Guideline
Low ---ambient Pressure Switch
Ye s
(For non ---Evolution system only)
No
Support Feet Recommended No
Thermal Expansion Valve (TXV)
Hard Shutoff
Ye s Ye s
Winter Start Control
Ye s
(For non ---Evolution systems only)
No
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split--- System Longline Application Guideline.
Table 2—Required Field--Installed Accessories for Heat Pumps
ACCESSORY
REQUIRED FOR LOW---AMBIENT
COOLING APPLICATIONS
(Below 55°F / 12.8°C)
REQUIRED FOR
LONG LINE APPLICATIONS*
(Over 80 ft. / 24.38 m)
REQUIRED FOR
SEA COAST APPLICATIONS
(Within 2 miles / 3.22 km)
Accumulator Standard Standard Standard
Compressor Start Assist
Capacitor and Relay
Ye s Ye s No
Crankcase Heater Yes
Ye s
No
Evaporator Freeze Thermostat
Ye s
(for non ---Evolution systems only)
No No
Isolation Relay
Ye s
(for non ---Evolution systems only)
No No
Liquid Line Solenoid Valve No
See Long--- Line Application
Guideline
No
Motor Master® Control or
Low Ambient Switch
Ye s
(for non ---Evolution systems only)
No No
Support Feet Recommended No Recommended
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split--- System Longline Application Guideline.