Bryant LEGACY 213R Service Manual Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 66
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
15
Table 3TechAssistt Diagnostics--at-- a --Glance
LED
Description ON OFF
Y Thermostat cooling call Yes No......... ........ ......
HPS High Pressure Switch Closed Open....... ......... ...
LPS Low Pressure Switch Closed Open....... .......... ...
230V AC Line Power Available Yes No...... ...... ......
Contactor Contactor Energized Yes No.. .......... ......
Compressor Compressor Running Yes No. .......... ......
CONTROL
POWER
Contactor Compressor230V
YHPS
LPS
Note: Follow arrows to first unlit LED in control (green) ladder or power (amber) ladder to determine problem area.
F o r contactor LED to be On, all control LEDs (green) as well as 230V LED (amber) must already be on, and contactor must operate
properly
Control Ladder
Power ladder
Indication
Possible Cause & Quick
Trouble---Shooting
Green LEDs Amber LEDs
Y HPS LPS 230V
Contac-
tor
Compressor
Off Off Off Off Off Off
--- No 230V power to unit
--- N o t h e r m o s t a t c a l l
--- Check 230V disconnect/ circuit breaker
--- Check 230V L1 & L2 wire connections
On Off Off --- --- Off Off --- H P S S w i t c h O p e n
--- Check pressures
--- Check HPS wire connections
On On Off --- --- Off Off --- L P S S w i t c h O p e n
--- Check pressures
--- Check LPS wire connections
On On On Off Off Off --- No 230V power to unit
--- Check 230V disconnect / circuit breaker
--- Check 230V L1 & L2 wire connections
On On On On Off Off --- C o n t a c t o r o p e n * * *
--- Check Contactor and replace if necessary
--- Check contactor wire connections
On On On On On Off --- Compressor not running*
--- Check for compressor protector trip, capacitor
fault, faulty connections or compressor fault.
SEE BELOW.
On On On On On On --- Compressor running --- O K
Off Off Off On Off Off --- No thermostat call, standby --- O K
Off Off Off On On Off
--- Contactor stuck closed,
compressor tripped
--- Check Contactor and replace if necessary
--- Check wire connections for shorts
Off Off Off On On On
--- Contactor stuck closed,
compressor running
--- Check Contactor and replace if necessary
--- Check wire connections for shorts
*Compressor not running: If all LEDs are on except the Compressor, this indicates that power is applied to the compressor but it is not running. Check the
following sequence:
1) Check all compressor wire connections
2) Check run capacitor and replace if necessary
3) Try starting compressor
4) If compressor LED does not come on, then leave unit in standby for up to four hours to allow thermal protector to reset, and all pressures to equalize
5) Try starting the compressor again
6) If compressor LED comes on, then turns off quickly, investigate starting issues such as low line voltage
7) If compressor LED never comes on, compressor may be faulty.
Fig. 8 Tech Assist Ladder Diagram