SYSTXBBECW01--A, SYSTXBBECN01--A& SYSTXBBECC01--AEvolutionr Connext ControlInstallation InstructionsA12479NOTE: Read the entire instruction manual
TP--LINK is a registered trademark of TP--LINK TECHNOLOGIES CO., LTD.U.S. Export Classification: EAR99.E2014 Bryant Heating & Co oli ng Systems 73
11. Safety ConsiderationsImproper installation, adjustment, alteration, service, maintenance, or use can causeexplosion, fire, electrical shock, or ot
2conditions, and other data are passed continually between components over theABCD bus. The result is a new level of comfort, versatility, and simplic
3A142153.1.1. Manually Adjust Time and Dated To set the HOUR, MINUTE, MONTH, DAY, or YEAR touch the featureyou wish to change.d Use the Up (Y) and Dow
43.1.2. Setup Time ZoneThe time zone can be selected by selecting the setup time zone from the menu.Then select the time zone for the location. Time z
53.2. Set Dealer InformationFrom the main screen, touch MENU, on the bottom of the control. The SERVICEicon allows you to upload your contact informat
64. Installation4.1. OverviewThis instruction covers installation of the Evolutionr Connext Control and theEvolutionr Wireless Access Point only. Phys
74.3. LocationELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personal injuryor death.Disconnect power before routing contro
8S Close to or in direct airflow from supply registers.S In areas with poor air circulation, such as behind a door or in an alcove.4.3.2. Remote Room
9Sensor 1 Sensor 2Sensor 3 Sensor 4Damper ControlModuleZS_Damper ControlModuleZS_CA032334.3.3. Smart Sensors (for zoning applications)Any zone may use
10NOTE: ABCD bus wiring only requires a four--wire connection; however, it isgood practice to run thermostat cable having more than four wires in the
11ELECTRICAL OPERATION HAZARDFailure to follow this warning could result in personal injuryor death.Before installing, modifying, or servicing system,
12S Adjust length and routing of each wire to reach each wire entry on theconnector backplate. Strip 1/4--in (6.4 mm) of insulation from each wire.S M
134.4.2. Damper Control Module (zoning systems only)All zoning wiring is run back to the Damper Control Module. Select a location nearthe furnace or f
14A12214A12215NOTE: Once Evolution Control is secured to wall with the backplate assembly(snapped together), care must be taken not to bend or break t
15A12213NOTE: Once the Evolution Connex Control is secured to wall with the backplateassembly (snapped together), care must be taken not to bend or br
16automatically energize the HUM output during a call for humidification. The N.O.relay contacts will be used to energize the humidifier. See fan powe
17A121785.2. Searching for Outdoor UnitThe Evolution Connex Control will then proceed to communicate with the outdoorunit by displaying “Searching for
18A131185.3. Indoor Evaporator SelectionIf a furnace is installed with a variable capacity heat pump or an Evolution V heatpump, a screen will appear
19A131195.4.1. Hydronic Heat ApplicationThe Evolution Connex Control supports 2 types of Hydronic Heat applications:1. Hot water coil in combination w
TABLE OF CONTENTSPAGE1.Safety Considerations 1...2.Introduction 1...
20A131175.5. Searching for SAM Module (If Applicable)“Searching for SAM Module” will appear on the screen to determine if a SystemAccess Module, used
21A121855.7. Filter Type SelectionThe installer will next be prompted to select the air filter type installed with theEvolution System. After the sele
22selected. If an incorrect selection was made, touch RE--INSTALL to restart theinstallation process.Example: SPP Equipment Summary ScreenA131275.11.
23approximately one minute per zone. The duct assessment will override a call forheat or cool.A duct assessment will automatically occur each day at a
246. Service MenuThe Service menus contain a set of vital information. This information enables theinstaller or service person to view a summary of wh
256.1. Equipment SummaryTouch EQUIPMENT SUMMARY to show indoor unit type and model number,outdoor unit type (and model number if a 2--stage unit), fil
26A14222NOTE: For Small Packaged Products (SPP), please use the following instructionsfor Set--up (Section 6.3), Checkout (Section 6.4), and Service (
27S Indoor:d Furnaced Fan coild PAC AC Indoord PAC HP Indoord GAS PAC Indoord GAS PHP IndoorS Outdoor:d AC/Heat pumpd PAC AC outdoord PAC HP outdoord
286.3.1.1. Auto Mode set upOnce the auto changeover option has been selected, touch SAVE.S Enable or Disable: Choose to enable or disable auto changeo
296.3.1.4. Reset factory defaultsThis option allows the installer to reset certain factory parameters. After theselections are made, touch SAVE.S Prog
TABLE OF CONTENTS (cont.)PAGE4.5.Mounting 13...4.5.1. Decorative Backplate 14...
30A142236.3.2.1. AirflowThis option allows the installer to select the appropriate air flow based on the needsof the installation. The QUIET airflow m
31After the selections are made, touch SAVE.S Cooling Airflow: Quiet, Comfort, EFF325, EFF350, or Maxd Default = ComfortS Dehumidify Airflow: Normal o
326.3.2.4. Fan Coil G--TerminalThis setup option selects desired operation when the R to G contact is closed on thefan coil control board. Under this
33A13230Shutdown: This setup option selects the change of state required for shutdown. .Select Normally Open or Normally Closed, and then save your se
34A142246.3.3. FurnaceFirst touch SETUP, then touch FURNACE to set up the parameters for the furnaceunit.A14225
356.3.3.1. Furnace AirflowSelects the airflow of the furnace when heating. EFFICIENCY is the airflow usedto meet specified ratings, COMFORT is a decre
36The dehumidify airflow, when set to NORMAL, the airflow is allowed to adjust toa minimum to satisfy the dehumidification call. When set to HIGH, the
37Min and Max limits are determined by the equipment size. These settings are notthe same as the zoning airflow limits.S Min. modulating limits: Minim
386.3.3.7. Furnace Dehumidifier DrainThis option selects the time the continuous fan turns off at the end of cooling inorder to drain the indoor coil
396.3.3.9. Furnace G--Terminal AlertUse the alert function to select the contact state for an alert. Select Normally Openor Normally Closed, and then
TABLE OF CONTENTS (cont.)PAGE6.Service Menu 24...6.1.Equipment Summary 25...
406.3.4. AC/Heat PumpFirst touch SETUP, then touch AC/HEAT PUMP to set up the parameters for theAC/Heat Pump unit.A142276.3.4.1. LatchingHigh Cool Lat
41S System in Controld The system will decide which stage should be running to satisfy the cool-ing demand.S High Coold Temperature above which only t
42S Cooling Lockout Temp: None, 45, 50 or 55 (_F)d Default = None6.3.4.3. Defrost IntervalTime interval at which defrost cycles can occur on a heat pu
436.3.4.6. AC/Heat Pump RPM MaxUsed with variable capacity heat pumps, this option clamps the operating speedof the heat pump to this maximum value. U
446.3.5. Heat Source LockoutFirst touch SETUP, then touch HEAT SOURCE LOCKOUTS to set up theparameters for the AC/Heat Pump unit.For hydronic heat app
45A142286.3.7. Zoning (If Applicable)First touch SETUP, then touch ZONING to set up the parameters for the zoningsystem (if applicable).A121916.3.7.1.
466.3.7.2. Zone OffsetsThis option allows actual temperature offset for each zone, allowing calibration (ordeliberate miscalibration) of each sensor.
47S Duct Assessment Time: Selectable between 12 AM and 11PMd Default = 1 PM6.3.8. AccessoriesFirst touch SETUP, then touch ACCESSORIES to set up the p
486.3.8.2. HumidifierWith this option, the installer has the option of selecting whether a humidifier isinstalled, to humidify with the fan in low spe
496.3.9. Utility CurtailmentUtility Saver is used to force the equipment to a lower stage (low or off) whenactivated by the utility company, typically
TABLE OF CONTENTS (cont.)PAGE6.3.3. Furnace 34...6.3.3.1.Furnace Airflow 35...
50A12194S Airflow: Selectable from Off to Max in 50 CFM incrementsd Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12)d Default = OffNOTE: Selected a
51A131226.4.1. Electric HeatIf you have a fan coil with electric heaters, this menu item will allow the heaters tobe exercised. With self--identifying
52motor turn on, the screen will show the current operating status of the furnace. Afterthe selections are made, touch START.S Low Heat: Selectable fr
53S High Cool Run Time: Selectable from 0 to 120 minutesd Default = 5 minutes6.4.5. Heat Pump HeatingThe heat pump heating mode can be exercised with
546.4.6. Heat Pump CoolingThe heat pump cooling mode can be exercised with this menu option. With a2--stage heat pump, a Low Cool Run Time and a High
556.4.8. VentilatorThe ventilator can be exercised through all of its operating speeds with this menuoption. To end the ventilator checkout, touch STO
56After proper damper operation has been verified, the installer can now check andverify that each Remote Room Sensor corresponds to the proper zone d
57A131296.5.1. Advanced DiagnosticsWhen viewing the Service Information screen, there is a button labeled ViewDiagnostics, which provides the top 3 mo
58A121976.5.3. Furnace StatusThe furnace status screen displays relevant information about the furnace operation.To return to the previous screen, tou
59A121996.5.5. Heat Pump StatusThe heat pump status screen displays relevant information about the heat pumpoperation. To return to the previous scree
TABLE OF CONTENTS (cont.)PAGE6.3.4.8.Brownout Disable 43...6.3.4.9.Low Air Multiplier 43...
60A122016.5.7. Last 10 System EventsThis screen will show the last 10 events that occurred throughout the system. Eachentry has the time and date inci
616.5.8. Run/Fault HistoryThis information is stored in the equipment circuit boards (if communicating) anddisplayed on the control. The indoor unit a
62A142306.5.10. Service Phone NumberThis menu item allows the installer to view the name and phone number that thehomeowner can call for future servic
636.6. Refrigerant Charging (Evolution Extreme Only)For variable speed heat pumps, a refrigerant charging menu is available to aid in theproper chargi
64Next, the installer will enter the SERVICE VALVE INFORMATION screen. Thecurrent liquid line subcool target, stabilization time, mode and speed in rp
65S Begin evacuation or refrigerant recovery as required for the procedure aftercontrol indicates the EXV is open. Power may be removed from heat pump
66Next, the installer will enter the SERVICE VALVE SUBCOOL screen. This screenwill show the current liquid line subcool target (in _F). To begin the c
676.7.2. Pump downBecause this system has an inverter controlled compressor, suction pressuretransducer and EXV, conventional procedure cannot be used
686.7.4. EXV PositionThis screen allows the installer to set the EXV position and monitor the suctionpressure.A142336.8. Dealer LogoTouch DEALER LOGO
69The PC/MAC software application to format the dealer logo and contactinformation can be found at:www.MyEvolutionConnex.Bryant.com/Evolution/download
TABLE OF CONTENTS (cont.)PAGE6.4.3. Hydronic 52...6.4.4. Air Conditioning 52...
70A14221NOTE: See the Owner’s Manual for additional details regarding the setup andconfiguration of the Utility Event feature.7.0 Wireless Set--upWith
71& Cooling Systems makes no representations or warranties, express or implied,including, to the extent permitted by applicable law, any implied w
72A13235S On the next screen look for the SSID of the router/access point. After beingselected, it will be outlined in faint blue. Then select NEXT.A1
73A13237S If a Wi--Fi security key is shown as on the right hand picture above then selectthe white bar and enter the security key, then select NEXT.S
74S After the control has connected to the network, go towww.MyEvolutionConnex.Bryant.comto register the unit and begin remoteaccess. This requires th
75A12490S Select the WIRELESS from the menu screenS Make sure the Wi--Fi connection is enabled, by touching ENABLED.S Touch SETUP A WI--FI CONNECTION
76SSID & Security KeyA12357d You may have to use the down arrow to scan to the next screen to find“myHVACxxxxxx”.A12116S Use the on screen keyboar
77A12117S The control will inform you if the connection is successful. If so, touch DONE.d If the connection is unsuccessful, verify that the proper i
78S If you have any issues, please contact your servicing dealer.S When the connection to the MyEvolution web server has been established, thestatus s
798. Appendix A -- Wiring DiagramsABCDABCDUser InterfaceGreen - Data AYellow - Data BWhite - COMRed - 24VACOATOptional RemoteRoom SensorHUMCOM24VHumid
TABLE OF CONTENTS (cont.)PAGE6.5.8. Run/Fault History 61...6.5.9. Model/Serial Numbers 61...
80ABCDABCDCYABCDConnectionUser Interface 1-Spd.Non-Communicating AC Green - Data AYellow - Data BWhite - COMRed - 24VACOptional
81ABCDABCDABCDConnectionUser Interface 1-Spd.Non-communicating HPGreen - Data AYellow - Data BWhite - COMRed - 24VACOptional
82ABCDZone ControlUser Interface &Smart Sensor(s)GreenYellowWhiteRedOATHUMCOM24VHumidifierConnectionABCD OATSensor(Optional)A B C D A B C DDamperC
83ABCDZone ControlUser Interface &Smart Sensor(s)GreenYellowWhiteRedOATHUMCOM24VHumidifierConnectionOATSensorA B C D A B C DDamperControlmoduleA B
84ABCDZone ControlUser Interface &Smart Sensor(s)GreenYellowWhiteRedA B C D A B C DDamperControlmoduleA B C DVariable-SpeedFan Coil1-Spd. HPHUMCYW
85RGFE Fan Coil or Variable Speed FurnaceA07114G Input Wiring for Blower Operation
86RGFE Fan Coil or Variable Speed FurnaceA07115G Input Wiring for System Shutdown
87NOTES
88NOTES (Cont.)
Comments to this Manuals