Bryant SYSTXBBECW01 Instruction Manual Page 38

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 37
28
6.3.1.1. Auto Mode set up
Once the auto changeover option has been selected, touch SAVE.
S Enable or Disable: Choose to enable or disable auto changeover mode
d Default = Enable
S Auto changeover time: Adjustable from 5 to 120 minutes
d Default = 30 minutes
6.3.1.2. Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. The deadband does not change when the user changes between
Fahrenheit (_F) and Celsius (_C). Ex: A 2_ deadband will be 2_For2_Canddoes
not change with units, _Fand_C. This can allow one setting to “push the other to
maintain this difference. When the correct deadband is set, touch SAVE.
S Deadband: Adjustable from 0 to 6_ F
d Default = 2_
6.3.1.3. Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. When the correct offsets are made, touch SAVE.
S Outdoor temperature: Adjustable from --5 to 5_F(--3to3_C)
d Default = 0_F
S Humidity: Adjustable from --10 – 10%
d Default = 0%
Page view 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 99 100

Comments to this Manuals

No comments