Bryant SYSTXBBECW01 Instruction Manual Page 19

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 18
9
Sensor 1 Sensor 2
Sensor 3 Sensor 4
Damper Control
Module
ZS_
Damper Control
Module
ZS_C
A03233
4.3.3. Smart Sensors (for zoning applications)
Any zone may use a Smart Sensor. It provides a temperature display and buttons to
adjust the desired temperature in that zone only. It also displays outdoor
temperature and indoor humidity sensed at the control. Only one Smart Sensor may
be used per zone. They cannot be averaged like Remote Room Sensors. If a Smart
Sensor is used in a zone, a Remote Room Sensor may also be used in the same
zone. The Remote Room Sensor has priority over the Smart Sensor. The Smart
Sensor will display the Remote Room Sensor temperature.
NOTE: Smart Sensors must be addressed to identify which zone it will control. See
Smart Sensor Installation Instructions for details.
4.4. Wiring Considerations
Ordinary thermostat wire is recommended. Use 22 AWG or larger for normal
wiring applications. Continuous wire lengths over 100 ft. should use 20 AWG or
larger.