Bryant SYSTXBBECW01 Instruction Manual Page 75

  • Download
  • Add to my manuals
  • Print
  • Page
    / 100
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 74
65
S Begin evacuation or refrigerant recovery as required for the procedure after
control indicates the EXV is open. Power may be removed from heat pump
after the control indicates READY TO EVACUATE.”
6.7. Refrigerant Charging Evolution V
For variable speed heat pumps, a refrigerant charging menu is available to aid in the
proper charging of the system. Enter the menu from the service screens by touching
REFRIGERANT CHARGING.
A14232
6.7.1. Charging
Within the CHARGING COOLING or HTG CHECK screens, the installer will
have the ability to enter the LINESET length and the VA P O R L I N E diameter.
After the selections are made, touch NEXT.
S Lineset: Selectable from 5 to 200 feet
S Vapor line: Selectable with various diameters by using the up and down
buttons
Next, the installer will enter the WEIGH IN screen to verify the current total charge
is accurate. Once the installer has confirmed, touch DONE.